ORD20121352-Chap32-Fire Code
COMMON COUNCIL - CITY OF MUSKEGO
ORDINANCE #1352
AN ORDINANCE TO AMEND CHAPTER 32
SECTIONS 32.13 B., 32.13 (C) g., 32.15 (C) c) 3. 5), 32.15 D. 2. i) AND 32.15 H. a)
OF THE MUNICIPAL CODE OF THE CITY OF MUSKEGO
(Fire Prevention code)
THE COMMON COUNCIL OF THE CITY OF MUSKEGO, WISCONSIN DO ORDAIN
AS FOLLOWS:
SECTION 1: The S-1 & S-2 designations in the table found in Chapter 32, Section 32.13
B., of the Municipal Code of the City of Muskego is hereby amended to read as follows:
OCCUPANCY TYPE 1 TYPE II TYPE III TYPE IV TYPE V
S-1 58,000 SF 58,000 SF 35,000 SF 35,000 SF 35,000 SF
S-2 58,000 SF 58,000 SF 35,000 SF 35,000 SF 35,000 SF
SECTION 2: Chapter 32, Section 32.13 (C) g., of the Municipal Code of the City of
Muskego is hereby amended to read as follows:
g. The FDC must include a 5” Storz connection with a Knox lock cover.
SECTION 3: Chapter 32, Section 32.15 (C) c) 3. 5), of the Municipal Code of the City of
Muskego is hereby amended to read as follows:
5) Appliances that automatically detect fire and/or products of
combustion are not required in buildings less than 25,000 sq. ft. that have
complete automatic fire sprinkler systems installed in accordance with NFPA
13, unless required by the AHJ. Note: State Codes may be more
restrictive.
SECTION 4: Chapter 32, Section 32.15 D. 2. i), of the Municipal Code of the City of
Muskego is hereby amended to read as follows:
i) Turning Radius. Curves and turn-arounds, solely leading to or within a fire
street, shall be designed for a forty-one eight (41 48) foot long fire truck with
an inside turning radius of 28.5 feet and outside turning radius of 49.5 feet
with a two-foot unobstructed overhang (see diagram herein for example). A
minimum 24-foot roadway of asphalt or concrete is needed around a turn to
accommodate this ordinance.
Ord. #1352 Page 2
Corner turning radius based upon 41-foot long fire truck with a 28.5-foot inside turning
radius and a 49.5-foot outside turning radius. This equates to needing a minimum of 21 feet
of pavement/concrete around a turn. A multiple turn may require greater pavement needs to
accommodate a proper turning radius. However, all other Muskego access ordinances apply
(Ex. Min. 24-foot access way for fire lane per Muskego ordinances applies).
SECTION 5: Chapter 32, Section 32.15 H. a), of the Municipal Code of the City of
Muskego is hereby amended to read as follows:
a) WHERE REQUIRED. Fire Department Standpipes shall be provided in all new
structures over two stories in height or 25,000 sq. ft. single story in accordance
with this section. All stairwells in buildings over one story will require standpipes.
SECTION 6: The several sections of this ordinance are declared to be severable. If
any section or portion thereof shall be declared by a decision of a court of competent
jurisdiction to be invalid, unlawful or unenforceable, such decision shall apply only to the
specific section or portion thereof directly specified in the decision, and not affect the
validity of all other provisions, sections or portion thereof of the ordinance which shall
remain in full force and effect. Any other ordinance whose terms are in conflict with the
provisions of this ordinance is hereby repealed as to those terms that conflict.
SECTION 7: This ordinance shall be in full force and effect from and after its passage
and publication.
PASSED AND APPROVED THIS ____ DAY OF ______ , 2012
CITY OF MUSKEGO
Kathy Chiaverotti, Mayor
Ord. #1352 Page 3
ATTEST: First reading: 01/10/2012
________________________
Clerk-Treasurer
Notice of Newly Enacted Ordinance Published: